Altusen KN1000 Manuel d'utilisateur Page 41

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 194
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 40
3. Browser Login
27
Shutdown
Method
There are three choices for the Shutdown method. Drop down the list
to select a choice. The meaning of each choice is described, below:
Wake on LAN: This is a Safe Shutdown and Restart option. If this is
selected, when an Outlet is turned Off, the KN1000 first sends a
message to the computer telling it to prepare for a shutdown; it then
waits for the amount time set in the Power Off Delay field to give the
OS time to close down before the computer is powered down to
standby mode.
Likewise, when the Outlet is turned On, the KN1000 waits for the
amount time set in the Power On Delay field, then sends an Ethernet
message to the computer connected to the Outlet telling the
computer to turn itself On.
Note: For Safe Shutdown and Restart, the computer must be running
Windows (98 or higher), or Linux, and the Safe Shutdown program
(available by download from our website), must be installed and
running on the computer. See System Requirements, page 6, for
details.
System after AC Back: This is a Safe Shutdown and Restart option. If
this is selected, when an Outlet is turned Off, the KN1000 first sends
a message to the computer telling it to prepare for a shutdown; it then
waits for the amount time set in the Power Off Delay field to give the
OS time to close down before the computer is powered down.
When the Outlet is turned On, the KN1000 waits for the amount time
set in the Power On Delay field, then sends power to the server.
When the server receives the power, it turns itself on.
Note: For Safe Shutdown and Reboot, the computer must be running
Windows (98 or higher), or Linux, and the Safe Shutdown program
(available by download from our website), must be installed and
running on the computer. See System Requirements, page 6, for
details.
Kill the Power: If this option is selected, the KN1000 waits for the
amount time set in the Power Off Delay field, and then turns the
Outlet's power Off. Turning the power off performs a cold (non-safe)
shutdown.
MAC In order to use either of the Safe Shutdown methods the MAC address
of the computer connected to the outlet must be filled in here.